Voltage Drop Calculator

Estimate how much voltage is lost along a wire run. Choose the wire, enter the one-way length and the load current.

How it works

Single-phase: VD = 2 × L × R × I ÷ 1,000. Three-phase: VD = 1.732 × L × R × I ÷ 1,000. L = one-way length in feet, R = conductor resistance in ohms per 1,000 ft, I = load current in amps. Percent drop = VD ÷ source voltage × 100. Resistance values are DC resistance at 75 °C from NEC Chapter 9, Table 8 (stranded unless marked solid).

Worked example: City of Chino: 2 × 210 ft × 0.78 ohm/kft × 3.167 A ÷ 1,000 = 1.038 V = 0.865% at 120 V. A 100 ft run of 12 AWG stranded copper (1.98) at 16 A drops 6.34 V, 5.28% of 120 V.

Assumptions

Frequently asked questions

How do you calculate voltage drop?

For a single-phase circuit, VD = 2 × one-way length (ft) × resistance (ohm per 1,000 ft) × current (A) ÷ 1,000. The City of Chino's example: 2 × 210 ft × 0.78 × 3.167 A ÷ 1,000 = 1.038 V, which is 0.865% of 120 V.

What is the resistance of 12 AWG copper wire?

NEC Chapter 9, Table 8 lists 1.98 ohm per 1,000 ft for stranded uncoated copper and 1.93 for solid, at 75 °C.

Is 3% voltage drop required by the NEC?

No. The 3% and 5% figures are in informational notes, which EC&M explains are explanatory material, not requirements. Local rules or project specs may still set limits; check with a licensed electrician.